KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, 3/4" NPT, 12" U, Hastelloy, Blind Cover, CSA

Price
$461.37 USD
Stock
5 In Stock

  • Process Connections: 3/4" MNPT

  • Insertion 'U' Length: 12", 23 cm

  • Adjustable Set Point Range: 0-254 feet/s, 0-77 meters/s

  • Input Power: 12-24 VDC & 115-230 VAC, 50-60 Hz

  • Operating Pressure (Maximum): 3480 psi, 24000 kPa, 240 bar

  • Temperature Range (Sensor): -55°C to 200°C, -67°F to 392°F

  • Wetted Materials:
    • Standard: Hastelloy C-276

  • Outputs/Communications:

    • Two Independent Relays (SPDT), 4-20 mA, Modbus

  • UL, CSA, Single Seal, NACE, NEMA 4
  • Specifications

    Accuracy

    • Flow Service: ± 1.0% of Set Point Velocity over Operating Range of ± 28° C (± 50° F)
    • Level Service: ± 0.64 cm (0.25")

    Applications

    • Flow
    • Interface
    • Level

    Approvals & Certifications

    • CRN - 316, 316L Stainless Steel - Canadian Registration Number 0F20731.5C: 2053 psi, 14,155 kPa, 142 bar
    • CRN - Hastelloy® C-276 - Canadian Registration Number 0F20731.5C: 2290 psi, 15,790 kPa, 158 bar
    • CRN - Titanium - Canadian Registration Number 0F20731.5C: 1165 psi, 8033 kPa, 81 bar
    • CSA - Local (Sensor) Enclosure Flameproof: Class I, Division 1, Groups B, C, D, Ex D IIB + H2 AEx D IIB + H2 (Class I, Zone 1, Group IIB + H2) Temperature Code: T3 Enclosure Typical 4, IP55 Single Seal Approved Per ANSI/ISA 12.27.01-2003
    • CSA - Remote Electronics Enclosure - Optional Flameproof: Class I, Groups B, C, D, Ex D IIB + H2 AEx D IIB + H2 (Class I, Zone 1, Groups IIB + H2) Temperature Code: T3
    • FM - Local (Sensor) Enclosure Flameproof: Class I, Division 1, Groups B, C, D Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C) Class I, Zone 1, AEx D IIB + H2 Enclosure Typical 4/IP55
    • FM - Remote Electronics Enclosure - Optional Flameproof: Class I, Division 1, Groups B, C, D Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C) Class I, Zone 1, AEx D IIB + H2 Enclosure Typical 4/IP55

    Communication

    • Modbus RTU Communication-Alarms, Flow Status & Diagnostics
    • RS-485 Using Kayden's Remote Control & Monitoring Software (RCMS) or other Modbus Compatible Software

    Cover - for Local Enclosure

    • Blind Cover - Flameproof
    • Glass Lens Cover - Flameproof

    Electronics - Standard Features

    • *Configurable only from the Kayden RCM Software
    • 100% Digital Design. Electronics are Environmentally Sealed
    • 4-Adjustable Independent Switch Point Timers
    • Automated Redundant Self-Test Diagnostics
    • Display Panel Lock-Out*
    • Easy Setup: No Mechanical Jumpers or Trim Pots
    • Incrementally Adjustable Heater Power (5% Steps) with Automatic Over-Range Protection
    • Intelligent User Interface with Push-Button & Constant Display of Operation (Flow/Level)
    • Start-Up Bypass Timer
    • Temperature Compensation
    • Temperature Mode*: Process Temperature may be Displayed/Graphed in Flow/Level Mode

    Enclosure Finish

    • Powder-Coated Polyester TGIC

    Enclosure, Body Details

    • 1" NPT Female Conduit Connection
    • Buna-N O-Ring on Cover

    Enclosure, Body Material

    • Copper-Free Aluminum (Does Not Exceed 0.4% Copper)

    Environmental Protection

    • IP55
    • IP67
    • NEMA 4X

    Input Power

    • 12-24 Vdc, 120-240 Vac, 50/60 Hz
    • Power Consumption: Maximum
    • Universal Power Input

    Insertion 'U' Length

    • 1.2" (3 cm)
    • 12" (30 cm)
    • 18" (46 cm)
    • 2" (5 cm)
    • 3" (7.5 cm)
    • 4" (10.1 cm)
    • 6" (15.2 cm)
    • 9" (23 cm)
    • Custom 'U' Lengths 2.5" to 120" (6.4 cm to 305 cm) Available in 1/2" (1.0 cm) Increments.

    NPT Connection

    • 1" NPT Male
    • 1/2" NPT Male
    • 1-1/2" NPT Male
    • 1-1/4" NPT Male
    • 2" NPT Male
    • 3/4" NPT Male

    Operating Pressure - Sensor

    • CRN - All Process Connections - 316/316 Stainless Steel - Canadian Registration Number 0F20731.5C: Maximum
    • CRN - All Process Connections - Hastelloy® C-276 - Canadian Registration Number 0F20731.5C: Maximum
    • CRN - All Process Connections - Titanium - Canadian Registration Number 0F20731.5C: Maximum
    • CSA - All Process Connections: Maximum

    Operating Temperature - Electronics

    • -55° to 65° C (-67° to 149° F)

    Operating Temperature - Sensor

    • -45° to 200° C (-50° to 392° F)

    Output

    • 4-20 mA (Thermal Signal, Scaleable) 120 Vac, Maximum

    Principle of Operation

    • Thermal, Calorimetric

    Remote Control & Monitoring Software

    • Adjust Relay Modes
    • Adjust Set Points 1 & 2
    • Load or Save User Settings
    • Lock or Unlock the Display Panel to Protect the Settings
    • Many Other Adjustable Features
    • Modify Heater Settings to Optimize Response Time
    • Monitor Operating Status
    • Operated Via a Personal Computer Locally or from a Remote Control Center
    • Visualize the Actions of the Process Via the Graphical Display

    Remote Electronics Enclosure & Cover

    • Blind Cover - Flameproof
    • Glass Lens Cover - Flameproof

    Response Time

    • Approximately 0.5 to 30 seconds

    Sensor, Probe Style

    • Insertion

    Storage Temperature

    • Product Should Be Stored in a Clean & Dry Environment between -30° & 60° C (-22° & 140° F)

    Switch Point Range

    • Gases:0.25 to 200 sfps, 0.08 to 60 SMPS - Standard Condition 21° C (70° F) at 14.7 psi (1 Atm)
    • Hydrocarbon-based Liquids: 0.01 to 5.0 FPS, 0.003 to 1.50 MPS
    • Water-based Liquids: 0.01 to 3.00 FPS, 0.003 to 0.9 MPS

    Switch Type

    • SPDT Sealed Relay Contacts Rated @ 4 Amps Resistive 230 Vac or 30 Vdc, Maximum

    Wetted Materials

    • 316, 316L Stainless Steel
    • All-Welded Construction
    • Hastelloy® C-276
    • Titanium

    Documentation

    Outline Drawings

    show more