810-RAC-0040-C1B0A-1E
Series: Kayden CLASSIC® 810 Flow, Level, Interface Switch & Transmitter Brand: Kayden InstrumentsKAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, 1/2" NPT, 4" U, SST, Blind Cover, CSA
Price
$777.58
USD
Stock
16 In Stock
- Process Connections: 1/2" MNPT
- Insertion 'U' Length: 4", 10.1 cm
- Probe width: 0.69", 1.75cm
- Adjustable Set Point Range: 0-254 feet/s, 0-77 meters/s
- Input Power: 12-24 VDC & 115-230 VAC, 50-60 Hz
- Operating Pressure (Maximum): 1,224 psi, 8,439 kPa, 84.4 bar
- Temperature Range (Sensor): -45°C to 200°C, -49°F to 392°F
- Local Enclosure: Aluminium Flameproof, 1" FNPT
- Cover: Flameproof Blind Cover
- Remote Electronics Enclosure and Cover: Not Required
- Wetted Materials:
- Standard: 316/316L Stainless Steel
- Outputs/Communications:
- Two Independent Relays (SPDT)
- 4-20 mA (Thermal Signal, Scalable)
- Modbus Communication via RS-485
- RCMS (Remote Control & Monitoring Software)
- Electronics - Standard Features:
- Automated Redundant Self-Test Diagnostics
- Display Panel Lock-Out
- Easy Set-up:
- No Mechanical Jumpers or Trim Pots
- Intelligent Push Button Interface
- Constant Display of Operation (Flow/Level)
- Temperature Compensation
- Start-Up Bypass Timer
- c CSA us (UL Standards), Single Seal, NACE, NEMA 4
Specifications
Brand
Accuracy
- Flow Service: ± 1.0% of Set Point Velocity over Operating Range of ± 28° C (± 50° F)
- Level Service: ± 0.64 cm (0.25")
Applications
- Flow
- Interface
- Level
Approvals & Certifications
- CRN - 316, 316L Stainless Steel - Canadian Registration Number 0F20731.5C: 2053 psi, 14,155 kPa, 142 bar
- CRN - Hastelloy® C-276 - Canadian Registration Number 0F20731.5C: 2290 psi, 15,790 kPa, 158 bar
- CRN - Titanium - Canadian Registration Number 0F20731.5C: 1165 psi, 8033 kPa, 81 bar
- CSA - Local (Sensor) Enclosure Flameproof: Class I, Division 1, Groups B, C, D, Ex D IIB + H2 AEx D IIB + H2 (Class I, Zone 1, Group IIB + H2) Temperature Code: T3 Enclosure Typical 4, IP55 Single Seal Approved Per ANSI/ISA 12.27.01-2003
- CSA - Remote Electronics Enclosure - Optional Flameproof: Class I, Groups B, C, D, Ex D IIB + H2 AEx D IIB + H2 (Class I, Zone 1, Groups IIB + H2) Temperature Code: T3
- FM - Local (Sensor) Enclosure Flameproof: Class I, Division 1, Groups B, C, D Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C) Class I, Zone 1, AEx D IIB + H2 Enclosure Typical 4/IP55
- FM - Remote Electronics Enclosure - Optional Flameproof: Class I, Division 1, Groups B, C, D Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C) Class I, Zone 1, AEx D IIB + H2 Enclosure Typical 4/IP55
Communication
- Modbus RTU Communication-Alarms, Flow Status & Diagnostics
- RS-485 Using Kayden's Remote Control & Monitoring Software (RCMS) or other Modbus Compatible Software
Cover - for Local Enclosure
- Blind Cover - Flameproof
- Glass Lens Cover - Flameproof
Electronics - Standard Features
- *Configurable only from the Kayden RCM Software
- 100% Digital Design. Electronics are Environmentally Sealed
- 4-Adjustable Independent Switch Point Timers
- Automated Redundant Self-Test Diagnostics
- Display Panel Lock-Out*
- Easy Setup: No Mechanical Jumpers or Trim Pots
- Incrementally Adjustable Heater Power (5% Steps) with Automatic Over-Range Protection
- Intelligent User Interface with Push-Button & Constant Display of Operation (Flow/Level)
- Start-Up Bypass Timer
- Temperature Compensation
- Temperature Mode*: Process Temperature may be Displayed/Graphed in Flow/Level Mode
Enclosure Finish
- Powder-Coated Polyester TGIC
Enclosure, Body Details
- 1" NPT Female Conduit Connection
- Buna-N O-Ring on Cover
Enclosure, Body Material
- Copper-Free Aluminum (Does Not Exceed 0.4% Copper)
Environmental Protection
- IP55
- IP67
- NEMA 4X
Input Power
- 12-24 Vdc, 120-240 Vac, 50/60 Hz
- Power Consumption: Maximum
- Universal Power Input
Insertion 'U' Length
- 1.2" (3 cm)
- 12" (30 cm)
- 18" (46 cm)
- 2" (5 cm)
- 3" (7.5 cm)
- 4" (10.1 cm)
- 6" (15.2 cm)
- 9" (23 cm)
- Custom 'U' Lengths 2.5" to 120" (6.4 cm to 305 cm) Available in 1/2" (1.0 cm) Increments.
NPT Connection
- 1" NPT Male
- 1/2" NPT Male
- 1-1/2" NPT Male
- 1-1/4" NPT Male
- 2" NPT Male
- 3/4" NPT Male
Operating Pressure - Sensor
- CRN - All Process Connections - 316/316 Stainless Steel - Canadian Registration Number 0F20731.5C: Maximum
- CRN - All Process Connections - Hastelloy® C-276 - Canadian Registration Number 0F20731.5C: Maximum
- CRN - All Process Connections - Titanium - Canadian Registration Number 0F20731.5C: Maximum
- CSA - All Process Connections: Maximum
Operating Temperature - Electronics
- -55° to 65° C (-67° to 149° F)
Operating Temperature - Sensor
- -45° to 200° C (-50° to 392° F)
Output
- 4-20 mA (Thermal Signal, Scaleable) 120 Vac, Maximum
Principle of Operation
- Thermal, Calorimetric
Remote Control & Monitoring Software
- Adjust Relay Modes
- Adjust Set Points 1 & 2
- Load or Save User Settings
- Lock or Unlock the Display Panel to Protect the Settings
- Many Other Adjustable Features
- Modify Heater Settings to Optimize Response Time
- Monitor Operating Status
- Operated Via a Personal Computer Locally or from a Remote Control Center
- Visualize the Actions of the Process Via the Graphical Display
Remote Electronics Enclosure & Cover
- Blind Cover - Flameproof
- Glass Lens Cover - Flameproof
Response Time
- Approximately 0.5 to 30 seconds
Sensor, Probe Style
- Insertion
Storage Temperature
- Product Should Be Stored in a Clean & Dry Environment between -30° & 60° C (-22° & 140° F)
Switch Point Range
- Gases:0.25 to 200 sfps, 0.08 to 60 SMPS - Standard Condition 21° C (70° F) at 14.7 psi (1 Atm)
- Hydrocarbon-based Liquids: 0.01 to 5.0 FPS, 0.003 to 1.50 MPS
- Water-based Liquids: 0.01 to 3.00 FPS, 0.003 to 0.9 MPS
Switch Type
- SPDT Sealed Relay Contacts Rated @ 4 Amps Resistive 230 Vac or 30 Vdc, Maximum
Wetted Materials
- 316, 316L Stainless Steel
- All-Welded Construction
- Hastelloy® C-276
- Titanium
Documentation
Data Sheets
Product Manuals
Application Considerations
Application Notes
- Application Note - Kayden 4-20mA Analog Output pdf 766 KB
- Application Note - Kayden Acid Level Detection pdf 1.4 MB
- Application Note - Kayden Fail Safe pdf 894 KB
- Application Note - Kayden High Level Detection Holding Tank pdf 996 KB
- Application Note - Kayden Leak Detection pdf 1.5 MB
- Application Note - Kayden Monitoring Digester Flow pdf 831 KB
- Application Note - Kayden Oil Water Separation pdf 1.2 MB
- Application Note - Kayden Pulp and Paper Digester Tank pdf 1.1 MB
- Application Note - Kayden Pulp and Paper Skimmer Tank pdf 829 KB
- Application Note - Kayden Pump Monitoring and Protection pdf 1.0 MB
- Application Note - Kayden Pump Monitoring and Protection Remote pdf 1.2 MB
Catalogs
Certifications & Approvals
Outline Drawings
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing F: Local Enclosure 2" MNPT pdf 312 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing H: Remote Enclosure 3/4" MNPT pdf 720 KB
- 2020 Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing A - Local Enclosure ½" MNPT pdf 190 KB
- 2020 Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing B - Local Enclosure 3/4" MNPT pdf 194 KB
- 2020 Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing C - Local Enclosure 1" MNPT pdf 181 KB
- 2020 Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing D - Local Enclosure 1 1/4" MNPT pdf 187 KB
- 2020 Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing E - Local Enclosure 1 1/2" MNPT pdf 188 KB
- 2020 Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing F - Local Enclosure 2" MNPT pdf 221 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing A: Local Enclosure 1/2" MNPT pdf 330 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing B: Local Enclosure 3/4" MNPT pdf 321 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing C: Local Enclosure 1" MNPT pdf 315 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing D: Local Enclosure 1-1/4" MNPT pdf 311 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing E: Local Enclosure 1-1/2" MNPT pdf 321 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing G: Remote Enclosure 1/2" MNPT pdf 738 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing I: Remote Enclosure 1" MNPT pdf 721 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing J: Remote Enclosure 1-1/4" MNPT pdf 714 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing K: Remote Enclosure 1-1/2" MNPT pdf 718 KB
- Legacy Outline Dimension Drawing - Kayden CLASSIC 810 - Drawing L: Remote Enclosure 2" MNPT pdf 723 KB