KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G, 1-1/2" 150# RF SST, 2.5" U, SST, Blind Cover, CSA

Price
$612.02USD
$0.78USD
On Sale
Stock
25+ In Stock

  • Process Connection:
    • Flanged Retractable Packing Gland Raised Face
    • 1-1/2" MNPT
    • ANSI: 150

  • Flange Materials: 316 Stainless Steel
  • Adjustable Set Point Range: 0-254 feet/s, 0-77 meters/s
  • Insertion 'U' Length: 2.5", 6.35 cm
  • Input Power: 12-24 VDC & 115-230 VAC, 50-60 Hz
  • Operating Pressure (Maximum): 3480 psi, 24000 kPa, 240 bar
  • Temperature Range (Sensor): -40°C to 160°C, -40°F to 320°F
  • Local Enclosure: Aluminium Flameproof, 1" FNPT
  • Cover: Flameproof Blind Cover
  • Remote Electronics Enclosure and Cover: Not Required
  • Wetted Materials:
    • Standard: 316 Stainless Steel

  • Outputs/Communications:
    • Two Independent Relays (SPDT), 4-20 mA, Modbus

  • UL, CSA, Single Seal, NACE, NEMA 4

Specifications

Accuracy

  • Flow Service: ± 1.0% of Set Point Velocity over Operating Range of ± 28° C (± 50° F)
  • Level Service: ± 0.64 cm (0.25")

Applications

  • Flow
  • Interface
  • Level

Approvals & Certifications

  • CRN - Canadian Registration Number - the Kayden Classic 814 Does Not have A CRN Number
  • CSA
  • CSA - Local (Sensor) Enclosure Flameproof: Class I, Division 1, Groups B, C, D, Ex D IIB + H2 AEx D IIB + H2 (Class I, Zone 1, Group IIB + H2) Temperature Code: T3 Enclosure Typical 4, IP55 Single Seal Approved Per ANSI/ISA 12.27.01-2003
  • CSA - Remote Electronics Enclosure - Optional Flameproof: Class I, Groups B, C, D, Ex D IIB + H2 AEx D IIB + H2 (Class I, Zone 1, Groups IIB + H2) Temperature Code: T3
  • FM
  • FM - Local (Sensor) Enclosure Flameproof: Class I, Division 1, Groups B, C, D Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C) Class I, Zone 1, AEx D IIB + H2 Enclosure Typical 4/IP55
  • FM - Remote Electronics Enclosure - Optional Flameproof: Class I, Division 1, Groups B, C, D Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C) Class I, Zone 1, AEx D IIB + H2 Enclosure Typical 4/IP55

Communication

  • Modbus RTU Communication-Alarms, Flow Status & Diagnostics
  • RS-485 Using Kayden's Remote Control & Monitoring Software (RCMS) or other Modbus Compatible Software

Cover - for Local Enclosure

  • Blind Cover - Flameproof
  • Glass Lens Cover - Flameproof

Electronics - Standard Features

  • *Configurable only from the Kayden RCM Software
  • 100% Digital Design. Electronics are Environmentally Sealed
  • 4-Adjustable Independent Switch Point Timers
  • Automated Redundant Self-Test Diagnostics
  • Display Panel Lock-Out*
  • Easy Setup: No Mechanical Jumpers or Trim Pots
  • Incrementally Adjustable Heater Power (5% Steps) with Automatic Over-Range Protection
  • Intelligent User Interface with Push-Button & Constant Display of Operation (Flow/Level)
  • Start-Up Bypass Timer
  • Temperature Compensation
  • Temperature Mode*: Process Temperature may be Displayed/Graphed in Flow/Level Mode

Enclosure Finish

  • Powder-Coated Polyester TGIC

Enclosure, Body Details

  • 1" NPT Female Conduit Connection
  • Buna-N O-Ring on Cover

Enclosure, Body Material

  • Copper-Free Aluminum (Does Not Exceed 0.4% Copper)

Environmental Protection

  • IP55
  • NEMA 4 / IP55

Flange Material

  • 316 Stainless Steel

Flange Size - 1-1/2" (DN40)

  • 1-1/2" (DN40) - 150#

Flange Size - 10" (DN250)

  • 10" (DN250) - 150#

Flange Size - 2" (DN50)

  • 2" (DN50) - 150#

Flange Size - 3" (DN80)

  • 3" (DN80) - 150#

Flange Size - 4" (DN100)

  • 4" (DN100) - 150#

Flange Size - 5" (DN125)

  • 5" (DN125) - 150#

Flange Size - 6" (DN150)

  • 6" (DN150) - 150#

Flange Size - 8" (DN200)

  • 8" (DN200) - 150#

Flange Type

  • Raised Face (RF)
  • RTJ - Ring Typical Joint

Input Power

  • 12-24 Vdc, 115-230 Vac, 50/60 Hz / Universal Power Input
  • Power Consumption: Maximum

Insertion 'U' Length

  • Custom 'U' Lengths 2.5" to 120" (6.4 cm to 305 cm) Available in 1/2" (1.0 cm) Increments.

Operating Pressure - Sensor

  • Maximum

Operating Temperature - Electronics

  • -55° to 65° C (-67° to 149° F)

Operating Temperature - Sensor

  • -40° to 160° C (-40° to 320° F)

Output

  • 4-20 mA (Thermal Signal, Scaleable)

Principle of Operation

  • Thermal, Calorimetric

Process Connection Style

  • Flanged Retractable

Remote Control & Monitoring Software

  • Adjust Relay Modes
  • Adjust Set Points 1 & 2
  • Load or Save User Settings
  • Lock or Unlock the Display Panel to Protect the Settings
  • Many Other Adjustable Features
  • Modify Heater Settings to Optimize Response Time
  • Monitor Operating Status
  • Operated Via a Personal Computer Locally or from a Remote Control Center
  • Visualize the Actions of the Process Via the Graphical Display

Remote Electronics Enclosure & Cover

  • Blind Cover - Flameproof
  • Glass Lens Cover - Flameproof

Response Time

  • Approximately 0.5 to 30 seconds

Retraction Assembly

  • Low Pressure with Security Chain, 316, 316L Stainless Steel (MWP 125 psi)
  • Low Pressure: 316, 316L Stainless Steel (MWP 50 psi)
  • Medium Pressure: 316, 316L Stainless Steel (MWP 500 psi)

Sensor, Probe Style

  • Insertion

Storage Temperature

  • Product Should Be Stored in a Clean & Dry Environment between -30° & 60° C (-22° & 140° F)

Switch Point Range

  • Gases: 0.25 to 200 sfps, 0.08 to 60 SMPS - Standard Condition 21° C (70° F) at 14.7 psi (1 Atm)
  • Hydrocarbon-based Liquids: 0.01 to 5.0 FPS, 0.003 to 1.50 MPS
  • Water-based Liquids: 0.01 to 3.00 FPS, 0.003 to 0.9 MPS

Switch Type

  • 2 SPDT Sealed Relay Contacts Rated @ 4 Amps Resistive 230 Vac or 30 Vdc, Maximum

Wetted Materials

  • 316, 316L Stainless Steel
  • All-Welded Construction
  • Highly Saturated Nitrile (Pressure Seal-sensor)

Documentation

Similar SKUs

814-RAA141AX-I0300-C1G0A1E
814-RAA141AX-I0300-C1G0A1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$783.86USD
25+ In Stock
KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G, 2" 150# RF SST, 30" U, SST, Lens Cover, CSA
814-RAA161AT-I1390-C1B0A1E
814-RAA161AT-I1390-C1B0A1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$356.23USD
9 In Stock
KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G, 4" 150# RF SST, 139" U, SST, Blind Cover, CSA
814-RAA141AX-I0130-C1B0A1E
814-RAA141AX-I0130-C1B0A1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$172.62USD
20 In Stock
KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G, 2" 150# RF SST, 13" U, SST, Lens Cover, CSA
814-RAA141AT-I0060-C1B0A1E
814-RAA141AT-I0060-C1B0A1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$426.85USD
25+ In Stock
KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G 2" 150# Flange, 6" U, SST, Blind Cover, CSA
814-RAA131AT-I1200-C1B1B1E
814-RAA131AT-I1200-C1B1B1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$365.64USD
23 In Stock
KAYDEN CLASSIC Flow, Level, Interface Switch, Modbus, P/G, 1-1/2" 150# RF SST, 120" U, SST, Blind Cover, Remote Electronics, CSA
814-RAA141AT-M0530-C1B0A1E
814-RAA141AT-M0530-C1B0A1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$645.76USD
25+ In Stock
KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G 2" 150# Flange, 53 cm U, SST, Blind Cover, CSA
814-RAA141AT-I0160-C1B0A1E
814-RAA141AT-I0160-C1B0A1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$630.85USD
14 In Stock
KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G 2" 150# Flange, 36" U, SST, Blind Cover, CSA
814-RAA131AT-I0150-C1B0A1E
814-RAA131AT-I0150-C1B0A1E
Kayden CLASSIC® 814 Flow, Level, Interface Switch & Transmitter
Kayden Instruments
$160.07USD
25+ In Stock
KAYDEN CLASSIC Thermal Flow, Level, Interface Switch, Modbus, P/G, 1-1/2" 150# RF SST, 15" U, SST, Blind Cover, CSA
show more